Upping the efficiency of pumps and fans

Oct. 6, 2005
Variable-speed drives gain favor as a way to minimize energy costs.

Jeff Theisen
Senior Drive Application Engineer
Rockwell Automation
Mequon, Wis.

 

Edited by Ken Korane

Variable-frequency drives, such as Rockwell Automation's PowerFlex units, save energy by controlling motor speed to match flow with demand.


Power requirements for outlet-damper systems gradually decrease with flow.


Variable-frequency drives significantly reduce power requirements as fan speed decreases.


Fan curves relate various operating parameters, based on the physical characteristics of a unit. This graph shows typical performance.


Manufacturers once assumed that energy costs were, for the most part, beyond their control. But such attitudes became outdated with the advent of power monitoring and control devices such as energy-efficient motors, sophisticated controllers and software, and variable-speed drives (VSD). They make sure that key processes use less energy, thus turning energy into a manageable expense.

The potential savings are mind-boggling. Domestic manufacturers spend more than $33 billion on electricity every year, with motor systems consuming approximately 63% of the total. More than half of the motors run either fans or pumps — key areas with significant potential for energy savings.

As a result, manufacturers are looking for ways to reduce power consumption for these applications. In general, any application in which pump or fan speed varies can potentially benefit from a variable-speed drive. Here's how to determine if a VSD is worth the price.

Most fan applications do not require maximum air movement all of the time. So, to vary airflow, managers use methods such as:

  • Cycling, typically used in residential settings and generally not applicable in industrial applications.
  • Outlet dampers with control louvers to restrict outlet airflow.
  • Variable inlet vanes that modify the physical characteristics of the air inlet, which changes airflow.
  • Variable-speed drives, which change the fan speed.

In industrial settings, variable-speed drives are generally the most effective way to control energy use because they regulate motor speed. Inlet vanes and outlet dampers only control airflow, not the motor.

As a rule, energy consumption in fans and pumps varies by the cube of motor speed, also called centrifugal load. For example, if the fan motor speed can be cut in half, energy consumption = ( 1 /2) 3 = 1 /8, meaning the energy used to power the motor actually decreases by 7 /8. The same rule applies to pumps.

To illustrate, let's compare outlet dampers and VSDs. Changing airflow or fan speed can affect the system's natural operating point, as well as a fan's efficiency and power requirements.

Outlet dampers affect a system by increasing resistance to airflow — stated mathematically as:

P = KQ 2

where P = pressure required to produce a given flow, K = resistance to airflow, and Q = airflow. Outlet dampers affect K. Power requirements for this type of system gradually decrease as flow decreases, as shown in the Outlet damper graphic.

Variable-frequency drives take advantage of changes in fan behavior as speed changes. This is quantified by a set of equations called affinity laws. These laws, for centrifugal pumps and fans, relate how changes in speed or geometry affect capacity or power consumption.

Q2 /Q1 = N2 /N1,

P2 /P1 = (N2 /N1) 2 , and

H2 /H1 = (N2 /N1) 3 ,

where N = fan speed, rpm; Q = flow, cfm; P = pressure, static in. H2O; and H = horsepower.

Reducing fan speed significantly reduces power requirements, as shown in the Variable speed graphic.

Comparing energy consumption when controlling airflow using outlet dampers to that used with variable-speed drives requires a load profile (based on the application) and a fan curve (supplied by the fan manufacturer). Based on the accompanying fan curve, let's assume the fan runs at 300 rpm and 100% flow = 100,000 cfm. Also assume the following load profile:

100% flow for 10% of the time; 80% flow for 40% of the duty cycle; 60% flow for 40% of the cycle; and 40% flow for the remaining 10%. For outlet dampers, the horsepower required for each operating point can be read from the fan curve. Multiplying the horsepower at each point by the percent of time the fan operates at this point produces the weighted horsepower. Weighted horsepower provides a glimpse into the amount of energy the motor uses to control airflow at each point in the duty cycle. Summing the calculations produces the total weighted horsepower, which represents the fan's average energy consumption over a complete cycle. The chart shows the complete results.

For variable-speed operation, the fan curve does not contain enough information to read horsepower values for all operating points. Therefore, affinity laws are incorporated into the calculations.

Substituting Q for N in the horsepower equation gives the following results:

Q2 = 80%, H2 = 18 hp; Q2 = 60%, H2 = 7.56 hp; Q2 = 40%, H2 = 2.24 hp.

From this data, one can calculate total weighted horsepower for variable-speed operations.

Results show the outlet damper has a weighted horsepower of 32.6, significantly higher than the variable-speed drive's 13.9 weighted horsepower. If the fan runs 730 hr/month and electricity averages $0.07/kW-hr, energy costs for the dampered fan would exceed $1,242. Meanwhile, the drive-controlled fan would use approximately $531 in electricity, representing a significant savings. Although the example is quite basic and does not consider motor and drive efficiency, it does illustrate the potential savings variable-speed operations offer.

Variable-speed drives offer similar energy savings for pumps. Pumps typically control flow with throttling valves or by changing pump speed. Just as calculations show the energy savings possible for fans, similar calculations estimate energy savings for pumps. Generally, reducing pump speed by 20% reduces motor horsepower by nearly 50%.

In addition to energy savings, variable-speed drives relieve stress on mechanical systems by starting gradually and ramping up to speed. The correct drive can also tighten process control.

Comparing energy consumption

A sample application compares outlet dampers and variable-speed drives under varying flow conditions. Results show the latter offers significant cost advantages.

Outlet-damper power requirements
Cubic feet per minute (cfm)
Duty cycle (%)
Horsepower (hp)
Weighted horsepower
100
10
35
3.5
80
40
35
14.0
60
40

31

12.4
40
10
27
2.7
Total
32.6

Variable-speed-drive power requirements
Cubic feet per minute (cfm)
Duty cycle (%)
Horsepower (hp)
Weighted horsepower
100
10
35
3.5
80
40
18
7.2
60
40
7.56
3.024
40
10
2.24
0.224
Total
13.948

Comparing costs
 
Outlet damper
Variable speed
Weighted horsepower
32.6
13.9
X kW/hp
0.746
0.746
X hr/month
730
730
= kW-hr/month
17,753
7,596
X electricity cost
$0.07
$0.07
Total cost
$1,242.73
$531.07

Harmonics And Power Quality

Power quality, including harmonics often associated with variable-frequency drives, can be an issue in facilities using large amounts of energy. Harmonics are deviations from the sinusoidal fundamental ac line voltage and current. Most electrical power in North America is delivered at 60 Hz, and harmonic frequencies operate at multiples of that. So, in a 60-Hz system, the second harmonic is 120 Hz, the third 180 Hz, and so on.

Harmonics distort the sinusoidal fundamental current and voltage. Higher harmonic amplitudes mean greater electrical-waveform distortion, which can ultimately damage equipment and lead to failure.

Unlike an ac motor operating across the power line, current drawn from a distribution transformer feeding a typical ac drive is far from sinusoidal. This is because the drive takes current from the transformer only at certain times during its cycle. This converts ac line voltage to a fixed dc voltage within the drive. The drive then pulse-width modulates the fixed dc voltage into variable-frequency voltage for the motor. The ac-to-dc conversion generates harmonics. Current flows during part of the cycle but is off during other parts of the cycle, creating an odd-looking current waveform. Distorted current creates distorted voltages.

Adhering to IEEE 519 standard helps ensure power quality by limiting the maximum current distortion caused by nonlinear loads. There are several methods recommended to reduce line-current harmonics created by drives. For instance, adding line reactors or passive filters reduces current harmonics. But under some conditions they also reduce the dc bus voltage within the drive in full-speed, full-load conditions. This means the drive cannot provide full power to the motor, limiting the motor's power output to about 95% of nameplate rating. Multipulse drives are other solution. No derating is necessary and the drives are generally less expensive than other mitigation methods.

MAKE CONTACT

For information on drives and energy efficiency, visit: ab.com/drives/energy_savings/index.html

For information on Rockwell Automation's PowerFlex 400, a drive developed specifically for fan and pump applications, visit: ab.com/drives/powerflex/400/index.html

Sponsored Recommendations

NEW Low Profile, Ultra Compact Power Supplies

March 13, 2024
Learn more HERE about Altech's Power supplies!

Altech's Liquid Tight Strain Relifs Catalog

March 13, 2024
With experienced Product Engineers and Customer Service personnel, Altech provides solutions to your most pressing application challenges. All with one thought in mind - to ensure...

Industrial Straight-Through Cable Gland

March 13, 2024
Learn more about Altech's cable glands and all they have to offer for your needs!

All-In-One DC-UPS Power Solutions

March 13, 2024
Introducing the All-In-One DC-UPS, a versatile solution combining multiple functionalities in a single device. Serving as a power supply, battery charger, battery care module,...

Voice your opinion!

To join the conversation, and become an exclusive member of Machine Design, create an account today!